Home>> Let's Talk Hydraulics>> Finding Zero, Part 3>>
InsaneHydraulics - Sergiy Sydorenko 2009-2010 All Ridghts Reserved
Home
Introduction
The Simple Test
Back-Engineering?
The Most Basic Basics
Let's Talk Hydraulics
Back-Engineer This!
Battlefield
Kaboom
Library
News Archive
Bla-Blaimer
Contacts
Guestbook
HomeIntroductionThe Simple TestBack-Engineering?The Most Basic BasicsLet's Talk HydraulicsBack-Engineer This!BattlefieldKaboomLibraryNews ArchiveBla-BlaimerContactsGuestbook |
    Well, here I am again, talking about the so very important matter of adjusting correct neutral swashplate position in closed circuit pumps. This third article concludes the "finding zero" series, so if you hadn't read the first two articles, you should do so before reading this one.

    Although nailing "zero" position of the swash plate is not a hard task, you must understand that there is no such thing as a "universal adjusting technique".  Steps you take to correctly adjust "the neutral" will vary greatly with the pump's control type and servo system design.  You must understand in detail the function of the control module used, and apply a good share of common sense before going into any adjustments, bearing in mind that there are situations when a correct null adjustment is impossible without disassembling the pump and/or replacing parts. And if you come across a pump or a control you are not familiar with, your best strategy is to look up technical info before performing any adjustments, at least when the pump is mounted on a machine (if you have it in your workshop, mounted on your test bench, and time isn't an issue, you may indulge yourself into tampering with them adjusting screws and backengineering, just don't forget - you broke it - you bought it!)

    The key words are - knowing of operation and common sense! For example, in pumps that have only one centering system, namely mechanical (like Rexroth A4VG pumps with DA control), there will be no need to install an external servo-pressure bypass, as the control directional vale does it for you when the solenoids have no signal current. In such systems the adjustment is dead straightforward - there is only one adjusting screw to adjust, although in some cases you might want to check the servo-pressures to see if the control directional valve is successfully bypassing the servo-cylinder. Let's not forget that there are controls which pressurize servo-cylinder sides, like the MS control, or that roportional non feedbak displacement controls have no hydraulic zero as well... Then there are pumps that have no centering systems at all (e.g. special HP pumps, which are now Bondioli & Pavesi, with free-floating servo-cylinder), and, obviously, when someone asks you to adjust the null in one of those, you should tell him to go take a hike.

     Adjustment procedures ("by-the-book" ones) will have predictable results only in case of pumps that have no or little wear. However, a technician should be ready to face a pump which is, let us say, "exhausted yet still kicking", marked by a significant play in the centering mechanisms, often both mechanic and hydraulic. In such cases, when an overhaul is not an option and the machine's operation is indisputably necessary, a technician should know that, most probably, the null will remain drifting, and the best thing that can be achieved is a close approximation to the so wanted zero, with the machine still (occasionally) running away... In such cases there isn't much you can do but explain to your client all the benefits of the drifting null condition, and also that you won't be held responsible for whatever the damage the machine might (will) cause in the future.

    In the first part I mentioned that I didn't like the "flow symmetricity" null adjusting technique. I still do not like it, but I must admit that in some cases it is the only technique to adjust the null correctly. As a rule, it happens with severely worn hydraulic positioning systems, which is often the case of small medium duty closed loop pumps, like Sauer series 40 with manual displacement controls. When these get worn out, there is a  HUGE play of the control lever between the centering springs, and in this case there's no use in looking for the right position of the adjustment bracket to equal the lines pressures - the null will drift because the control lever and the attached control spool are loose. In this case, your best reference will be the maximum flow, and you will have to lock the bracket in a position, where the pump will present equal maximum flows in both directions, and forget about the exact null (sad but true...). In most cases this is not a big problem, actually, because on the actual machine the control joysticks, that are attached to the pump's control lever, are centered by their own set of springs, thus "overriding" whichever null position play the control might have.

    As you can see,  hydrostatic transmission null adjustment involves various distinctive techniques, but some previous study and a little bit of sound judgment makes the job a hundred times easier. Watch you step, though! Most of the times these procedures are simple, yet they should never be applied without complete understanding of the theoretical part behind the pump's operation!

    I TRULY hope that this short series made the sensitive null adjustment matter a little bit clear-er..

    Should you have any questions, please, do not hesitate to ask.